ACC Users Group › ACC Users Group Discussion Forums › Inspection › Steam Duct Support Failure › Reply To: Steam Duct Support Failure
May 26, 2020 at 2:33 pm
#2255
powerplantdocs
Participant
Have witnessed this occurring at a facility in Nevada. If the bolts for these stiffeners are shearing then I would advise that you look at the Condensate headers for freedom of movement. There is only one fixed point for each CCM and SDM provided to limit the direction of thermal growth. If the CCM and SDM are not allowed to “grow” and slide in the intended direction then stresses may be applied elsewhere. Drop me a line. Marty mcyr@powerplantdocs.com